General Terms and Conditions for the Installation of HARO Quality Flooring over Underfloor Heating
All HARO floor coverings are suitable for installation over underfloor heating. The type of heat generation (warm water, electric heating, etc.) is not decisive for the suitability for use over underfloor heating.
Requirements on the underfloor heating system:
- The surface of the installed floor covering must not exceed a maximum temperature of 25°C at any point in time during operation of the underfloor heating system.
- The total thermal resistance should not exceed 0.15 m²K/W.
- The heat must be distributed evenly over the entire surface.
- If multiple heating circuits exist, the floor covering may only be installed without expansion joints if all heating circuits are run at the same temperature.
- The heat-up record and the CM measurements (measuring points!) must have been conducted at approximately the same time and must meet the requirements specified by Hamberger (see Laying Instructions).
Requirements on the 3-step preparatory measures for installation:
HARO Tip: It is strongly recommended to have this work and the preparatory measures indicated above performed by a qualified expert!
Requirements on the floor construction: The total thermal resistance is the sum of the individual thermal resistance values of the floor covering and footfall sound insulation used. The total thermal resistance should not exceed 0.15 m²K/W.
Some benchmark figures:
| Floor covering: |
Thickness |
Thermal resistance |
| HARO PARKETT 2500 |
11 mm |
0.076 m²K/W |
| HARO PARKETT 4000 |
13 mm |
0.110 m²K/W |
| HARO PARKETT Carre |
16 mm |
0.140 m²K/W |
| HARO TRITTY 75/100 |
7-8 mm |
0.063 - 0.069 m²K/W |
| HARO CORKETT* |
11 mm |
0.150 m²K/W |
| HARO LINETT* |
10 mm |
0.085 m²K/W | *) insulation underlay not required!
| Sound insulation |
|
|
| Silent Pro® |
3 mm |
0.030 m²K/W |
| Silent Pro® |
2 mm |
0.025 m²K/W |
| Silent Pro® |
1 mm |
0.013 m²K/W |
| Corrugated cardboard |
2.5 mm |
0.040 m²K/W |
| Roll-out cork underlay |
2 mm |
0.040 m²K/W |
| no insulation underlay |
0.0 m²K/W |
Calculation examples:
| HARO PARQUET 2500 |
Corrugated cardboard 2.5 mm |
|
| 0.076 m²K/W |
+0.040 m²K/W |
= 0.116 m²K/W |
| |
| HARO PARQUET 4000 |
Silent Pro® (3 mm) |
|
| 0.110 m²K/W |
+0.038 m²K/W |
= 0.140 m²K/W |
| |
| HARO TRITTY 75/100 |
Roll-out cork underlay 2 mm |
|
| 0.063 - 0.069 m²K/W |
+0.040 m²K/W |
= 0.109 m²K/W |
| |
| HARO CORKETT |
|
|
| (insulation underlay not required) |
= 0.150 m²K/W |
| |
| HARO LINETT |
|
|
| (insulation underlay not required) |
= 0.085 m²K/W | |